Generator not starting on Natural GasUpdated a month ago
Generator Will Not Start on Natural Gas – Troubleshooting Guide
If your generator will not start when using Natural Gas, follow the steps below to identify and resolve the most common causes.
⚠ Safety Notice:
Do not operate the generator if you smell natural gas before startup, as this may indicate a leak.
Step 1: Confirm Proper Startup Procedure
Make sure the generator is being started using the correct Natural Gas startup procedure.
(CLICK HERE) To Review Start up Procedures If Needed
Step 2: Verify Battery Connection
Generators are shipped with the negative battery terminal disconnected for safety during shipping.
Confirm that the battery is properly connected before attempting to start the generator.
(CLICK HERE) On instructions how to connect battery If Needed
Step 3: Test the Battery Voltage
If using the push-button start, check the battery voltage.
Recommended readings:
13.5 volts when not under load
11.5 – 12 volts under load
Recharge or replace the battery if the voltage is too low.
Step 4: Inspect Natural Gas Hose and Connections
Inspect the natural gas hose and fittings for:
Damage
Loose connections
Signs of gas leaks
Also inspect the second-stage regulator, which is typically located behind the generator panel.
Step 5: Verify Natural Gas Supply Pressure
Confirm that your natural gas supply is producing the correct fuel pressure.
The required natural gas inlet pressure should be:
6.0 – 9.0 inches of water column (WC)
Insufficient or excessive pressure may prevent the generator from starting or running properly.
Step 6: Confirm Natural Gas Supply Capacity (BTU Requirements)
Your natural gas supply must provide enough BTU capacity to operate the generator at full load.
| Generator Model | Required BTU (Full Load) |
|---|---|
| XP7000IHT | 121,000 BTU |
| XP9500IHT | 176,000 BTU |
| XP11000IHT | 204,000 BTU |
| XP13000HXT | 225,000 BTU |
| XP15000HXT / XP15000HXT+ | 278,000 BTU |
| XP16000iHT | 295,000 BTU |
| XP28000iHT | 327,000 BTU |
If the gas supply cannot meet the required BTU demand, the generator may fail to start or stall under load.
Step 7: Verify Fuel Selector Switch Position
Ensure the fuel selector switch is fully set to the Natural Gas position.
If the selector switch is not fully engaged, the generator may not receive fuel.
Step 8: Inspect the Spark Plug
Remove and inspect the spark plug for:
Carbon buildup
Damage
Weak spark
Replace the spark plug if necessary using the NGK spark plug recommended for your generator model.
Step 9: Verify Choke Position
Confirm the choke is positioned correctly during startup.
Note: EH series generators use a manual choke.
Step 10: Test Other Fuel Sources
If possible, try starting the generator using gasoline or propane.
If the generator runs correctly on other fuel sources, the issue may be related to:
Natural gas supply pressure
Fuel selector switch
Natural gas regulator or hose
Potential Parts That May Require Replacement
Based on troubleshooting results, one or more of the following components may require replacement.
Natural Gas Hose
Replace the hose if:
Fittings are damaged
Gas leaks are present
The hose shows signs of cracking or wear
Second-Stage Regulator
Replace the regulator if:
It is damaged
Gas leaks are present
It is not regulating natural gas pressure correctly
Fuel Selector Switch
Replace the fuel selector switch if:
The knob or assembly is broken
The switch cannot fully engage
The generator runs when bypassing the selector switch
Natural Gas Fittings
Replace fittings if:
They are damaged
Gas leaks are present
The fittings are not seating correctly
Generator Will Not Start on Any Fuel Source
If the generator will not start on gasoline, propane, or natural gas, check the following:
Inspect the electric start system
Confirm the generator attempts to crank
Check for spark
Verify the engine oil level
Look for any sensor warning lights on the control panel
AI Search Triggers (Internal Use)
generator won't start natural gas
natural gas generator troubleshooting
generator natural gas pressure issue
generator NG fuel supply problem
generator natural gas BTU requirement
generator natural gas regulator issue
generator natural gas hose leak
generator hard starting natural gas
✅ Support Tip:
Most natural gas starting issues are related to insufficient gas pressure or BTU supply from the home gas line. Always confirm the gas supply pressure (6–9 in. WC) and BTU capacity meet the generator’s requirements.